Free and fast online tools to help you plan your inspection and compliance processes. Your information is calculated solely in your browser — no registration or email required.
↓ 52 calculation tools — click the title to open. Each tool also has a detailed guide page.
⚡Reactive Power & Compensation Penalty RiskInductive/capacitive ratio and penalty threshold
Reactive Power & Compensation Penalty Risk
Enter the energy values from your monthly bill; see your inductive/capacitive reactive ratios, approximate power factor (cosφ), and your status according to penalty thresholds.
🔌Compensation Capacitor PowerkVAr required for the target cosφ
Compensation — Required Capacitor Power
Calculate the reactive power (kVAr) required to achieve the target power factor (cosφ). This complements the reactive penalty risk tool: a tool that identifies the problem, and a tool that sizes the solution.
🔺Power Triangle Converter (P/Q/S/cosφ)Active power S, Q and phase angle
Power Triangle Converter (P / Q / S / cosφ)
Enter the active power (P) and power factor (cosφ); instantly view the apparent power (S), reactive power (Q), and phase angle (φ).
⚡Three-Phase Power Calculator (kW/kVA)From U, I, cosφ, we have P, S, and Q.
Three-Phase Power Calculator (kW/kVA)
Calculate active (kW), apparent (kVA), and reactive (kVAr) power from voltage, current, and power factor.
🔥Cable/Line Power Loss (I²R)Conductor loss and annual energy
Cable/Line Power Loss (I²R)
Calculate the conductor power loss (I²R) in a transmission/distribution line; you can also see the annual energy loss and cost if desired.
💵Energy Consumption & CostMonthly/annual kWh and TL
Energy Consumption & Cost
Calculate the monthly and annual energy consumption and electricity cost of a load (motor, lighting, appliance).
📈Power Factor Correction GainCurrent and I²R loss reduction
Power Factor Correction Gain (Current & Loss)
See how much the line current and I²R losses decrease when you improve the power factor (cosφ). Quantify the benefit of compensation.
📉Voltage Drop & Cable Cross-SectionLine %ΔU, %3–5 boundary control.
Voltage Drop & Cable Cross-Section
Calculate the approximate percentage voltage drop of a line and compare it to the %3–5 reference limits.
🧵Cable Load & Correction (Ampacity)Temperature/grouping corrected capacitor
Cable Load & Correction Factor (Ampacity)
Adjust your cable's catalog current carrying capacity according to ambient temperature and grouping; check if it meets the design current.
🔧Fuse/Circuit Breaker Selection (Ib≤In≤Iz)Suitable standard rated current
Fuse/Circuit Breaker Selection (Ib ≤ In ≤ Iz)
Determine the appropriate standard rated current (In) based on the design current and cable capacity (overcurrent protection coordination).
🧱Protective/Grounding Conductor Cross-SectionAdiabatic minimum cross-section
Protection/Grounding Conductor Cross-Section (Adiabatic)
Calculate the minimum protective conductor cross-section required for a given fault current and tripping time using an adiabatic equation.
📏Minimum cable cross-section from target ΔU.The smallest cross-section allowed for %ΔU
Minimum cable cross-section from target voltage drop.
Find the minimum cable cross-section required based on the allowed voltage drop percentage. This is the inverse of the voltage drop tool.
🔥Cable Short Circuit Withstand (I²t)Can the cable survive a short circuit?
Cable Short Circuit Withstand (I²t)
Check whether a cable can thermally withstand a potential short-circuit current and tripping time.
🛡️Selecting a Residual Current Device (RCD)IΔn threshold and relay type
Selecting a Residual Current Device (RCD)
View the recommended leakage current threshold (IΔn) and relay type according to the intended use and load type.
🔬Insulation (Megger) Resistance LimitsTest voltage and minimum MΩ
Insulation (Megger) Resistance Limit Values
Check the applicable test voltage and minimum insulation resistance based on the circuit's nominal voltage; compare this to your measured value.
⚠️Arc Flash AwarenessRisk priority and work need
Arc Flash — Awareness Assessment
Assess your arc flash risk awareness based on your system conditions. This tool does not calculate energy (cal/cm²).; It prioritizes only the need for detailed study.
💥Short Circuit Power & Impedance (Sk/Zk)Ik to Sk and network impedance
Short Circuit Power & Impedance (Sk / Zk)
Calculate the short-circuit power (Sk) and the mains impedance (Zk) from the short-circuit current at a point; or vice versa.
🌩️SPD / Surge Arrester Selection GuideType according to installation location and risk.
SPD / Surge Arrester Selection Guide
Determine the appropriate type of surge protector (SPD) based on the installation location, lightning risk, and grounding system.
🔀Selectivity / Coordination Pre-CheckSelectivity based on current ratio.
Selectivity / Coordination Pre-Check
Preliminarily assess the possibility of selectivity based on the rated current ratio of the upper and lower protective devices.
🏭Transformer Load & Short Circuit CurrentFull load and approximate short-circuit current
Transformer Full Load & Short Circuit Current
Calculate the full-load current and approximate short-circuit current in the transformer secondary (preliminary information for panel/breaker selection).
⚖️Transformer Load Ratio (%)% load and current according to rated power.
Transformer Load Ratio (%)
Calculate the transformer's percentage load and secondary current based on its rated power; identify over/under loads.
♻️Transformer Loss & Efficiency (Cu+Fe)Iron + copper loss → efficiency
Transformer Loss & Efficiency (Iron + Copper)
From the idle (iron) and load (copper) losses on the label, calculate the total loss and efficiency at your chosen loading configuration.
📐Transformer Voltage Regulation (%)Secondary voltage drop under load
Transformer Voltage Regulation (%)
Calculate the secondary voltage drop (regulation) under load from the short-circuit voltage and copper loss.
💸Annual Transformer Loss CostIdle + load loss → TL/year
Annual Transformer Loss Cost
Calculate the transformer's annual energy loss and cost, taking into account no-load (iron) and load (copper) losses.
🌡️Transformer Cooling / Oil Preliminary AssessmentPriority for fat test / thermography
Transformer Cooling / Oil — Preliminary Assessment
Determine your priority for oil testing/thermography for the transformer based on load, temperature, and maintenance indicators. This preliminary assessment is for awareness purposes.
🔋Generator Sizing (kVA)Power based on load, concurrency, and margin.
Generator Sizing (kVA)
Calculate the approximate generator power (kVA) based on total load, power factor, simultaneity, and spare margin.
⛽Generator Fuel Consumption & AutonomyHourly/daily diesel + tank autonomy
Generator Fuel Consumption & Tank Autonomy
Calculate hourly/daily diesel consumption and tank autonomy based on generator load and specific fuel consumption.
🔌UPS Battery Autonomy TimePower supply time depends on load and battery.
UPS Battery Autonomy Time
Calculate the approximate power supply (autonomy) time of the UPS based on load and battery information.
🪫UPS Battery Sizing (Ah)Required capacity from the requested time
UPS Battery Sizing (Required Ah)
Calculate the battery capacity (Ah) required for the desired autonomy time. This is the reverse of the UPS autonomy tool: it gives the time and finds the capacity.
📊Demand Force & SimultaneityDemand power and current from installed power
Demand Force & Simultaneity
Calculate the plant's demand power and approximate demand current by multiplying your installed (connected) power by the simultaneity factor (prior information on main supply, meter, and transformer sizing).
⚙️Motor Full Load CurrentPower/voltage/cosφ/efficiency from rated current
Motor Full Load Current
Calculate the full-load (nominal) current based on motor power, voltage, power factor, and efficiency. The exact value is on the motor label.
🔄Engine Starting Current (DOL)Starting current in direct starting
Engine Starting Current (DOL)
Calculate the approximate starting current drawn by the motor during direct starting (DOL).
🛡️Thermal Relay AdjustmentRecommended setting for overload relay.
Thermal (Overload) Relay Setting
Find the recommended setting value for the thermal overload relay based on the motor's full load current.
🎛️Selection of Departure MethodDOL / star-delta / softstarter / VFD
Engine Starting Method Selection
See the appropriate starting method according to engine power and load type (DOL, star-delta, softstarter, VFD).
🔌Motor Compensation (kVAr)Engine power factor correction
Motor Compensation (kVAr)
Calculate the capacitor power required to bring a motor's power factor to its target value.
🌍Grounding Resistance (Rod Electrode)Resistance depends on ρ and rod size.
Grounding Resistance (Rod Electrode)
Calculate the approximate grounding resistance of a single-rod electrode from the soil resistivity and rod dimensions.
🌩️Lightning Risk — Preliminary AssessmentPrioritize protection for your building.
Lightning Risk — Preliminary Assessment
Select the essential features of your building; determine your priority in terms of lightning protection. This preliminary assessment is for awareness and prioritization.
🗼Lightning Protection Level (LPL) ParametersRolling ball, net, landing gear
Lightning Protection Level (LPL) Parameters
Select the protection level according to TS EN 62305-3; view the rolling sphere radius, mesh spacing, and down conductor spacing. Optional: calculate the protected radius on the ground by entering the pole/rod height.
🔻Number of Downstream (Downstream) ConductorsNumber according to Environment and LPL
Number of Downstream (Downstream) Conductors
See the approximate number of down conductors required according to the building environment and protection level (LPL) (TS EN 62305-3).
🔗Main Grounding / Equipotential Busbar Cross-SectionPE and busbar from the phase section.
Main Grounding / Equipotential Busbar Cross-Section
View the cross-section of the protective conductor (PE) and the main equipotential bonding conductor from the cross-section of the largest phase conductor (TS EN 60364-5-54).
💡Lighting Compliance (EN 12464-1)Reference luxury and measurement comparison.
Lighting Compliance (EN 12464-1)
Select the area/task type; view the EN 12464-1 reference illuminance level (Em). Optionally, enter and compare the measured lux.
🔆Number of Luminaires (Lumen Method)N = E·A/(Φ·UF·MF)
Number of Luminaires (Lumen Method)
Calculate the target illumination level and the number of luminaires required for the area using the lumen method.
📊Lighting Power Density (W/m²)Installed power/area + lm/W efficiency
Lighting Power Density (W/m²)
Calculate the power density (W/m²) and, if desired, the average efficiency (lm/W) by dividing the installed lighting power by the area.
💰LED Conversion Payback (ROI)Annual savings and repayment
LED Conversion Payback (ROI)
Calculate the annual savings and payback period of converting existing fixtures to LED.
🔦Emergency/Escape Lighting (EN 1838)Minimum luxury + measurement comparison
Emergency/Escape Lighting (EN 1838)
Check the EN 1838 minimum emergency lighting reference according to the area type; compare it to the lux you measured.
🎚️VFD Energy Saving (Affinity)Pump/fan savings through speed control.
VFD (Frequency Inverter) Energy Saving
Calculate the approximate energy savings achievable with velocity control (VFD) in a pump/fan application using the law of affinity.
☀️Annual Production Forecast for Solar Power PlantskWp → annual kWh and revenue
Annual Solar Power Generation Estimate
Estimate the approximate annual output of a rooftop/ground-mounted solar power system from installed capacity (kWp), equivalent sunshine hours, and performance ratio.
💧Pump Motor Power (Hydraulic)Flow rate/height and shaft and motor power
Pump Motor Power (Hydraulic → Shaft / Motor)
Calculate the pump's hydraulic power, shaft power, and required motor power from the flow rate and head.
💹Simple Return on Investment (ROI)Payback period and return
Simple Return on Investment (Payback / ROI)
Calculate the payback period and simple return on an energy efficiency investment.
🔊Daily Noise Exposure (LEX, 8h)Action values 80/85/87 dB(A)
Daily Noise Exposure (LEX, 8h)
Calculate the daily noise exposure, normalized to 8 hours, from the measured noise level and exposure time, and compare it to the action values.
🔬Insulation Polarization Index (PI/DAR)Insulation with time-resistance ratio
Insulation Polarization Index (PI/DAR)
Calculate the polarization index (PI) and dielectric absorption ratio (DAR) from time-lapse insulation resistance measurements; evaluate the insulation condition.
📳Vibration Exposure A(8)Arm/whole body action limit
Vibration Exposure A(8)
Calculate daily vibration exposure normalized to 8 hours from vibration magnitude and exposure time; compare with action/limit values.
These guidelines are for general information purposes only and do not constitute a binding inspection/declaration of conformity. Definitive results will be determined by on-site inspection in accordance with relevant legislation and standards. For detailed evaluation, please refer to the relevant documentation. You can get an offer..