Motor Kompanzasyonu İçin Kaç kVAr Gerekir?

Capacitor power required for the motor. Qc = P·(tanφ₁−tanφ₂) It is found with the capacitor directly connected to the motor terminal. Overcompensation should be avoided. — The capacitor should not exceed the motor's no-load magnetization strength (risk of self-excitation); therefore, the target cosφ is generally kept at 0.95.

Qc = P·(tanφ₁ − tanφ₂) · target cosφ ≤ ~0.95 in the motor
Example calculation: For a 15 kW motor, cosφ 0.80 → 0.95 → Qc = 15×(0.75−0.329) ≈ 6.3 kVAr (avoid overcompensation at the motor terminal).

Motor Compensation (kVAr)

Calculate the capacitor power required to bring a motor's power factor to its target value.

Required capacitor
Notes: Qc = P·(tanφ₁−tanφ₂). Avoid overcompensation in the capacitor directly connected to the motor terminal. — The capacitor power should not exceed the motor's no-load magnetization (reactive) power; otherwise, there is a risk of self-excitation and overvoltage. Therefore, the target cosφ is generally kept around 0.95.

How is it calculated?

  1. Enter the engine power (kW).
  2. Enter the current and target cosφ values.
  3. Press Calculate.

Frequently Asked Questions

How is engine compensation calculated?
Qc = P·(tanφ₁−tanφ₂), where motor power and current/target power factor are used.
Why is overcompensation dangerous in an engine?
Excess capacitors directly connected to the motor terminal can lead to self-excitation and overvoltage.
What should the target cosφ be for the motor?
To prevent self-excitation, the target for motor individual compensation is generally kept around 0.95.