How to Calculate Grounding Resistance? (Rod Electrode)

Grounding resistance of the vertical rod electrode R = ρ/(2πL)·(ln(8L/d)−1) It is found using: soil resistivity (ρ), rod length (L) and diameter (d). For example, for ρ=100 Ω·m, 3 m length, 16 mm diameter, R ≈ 33.5 Ω. Soil resistivity is determined by measurement (Wenner).

R = ρ/(2πL)·(ln(8L/d) − 1) [Ω]
Example calculation: ρ=100 Ω·m, 3 m long, 16 mm diameter rod → R = 100/(2π×3)·(ln(8×3/0.016)−1) ≈ 33.5 Ω. Longer/more rods are needed for lower resistance.

Grounding Resistance (Rod Electrode)

Calculate the approximate grounding resistance of a single-rod electrode from the soil resistivity and rod dimensions.

Grounding resistance
The ρ used
Notes: R = ρ/(2πL)·(ln(8L/d)−1) (BS 7430 / IEEE 142 — vertical bar). Soil resistivity ρ is determined by measurement (Wenner 4-prong method). And it varies depending on the season/humidity; typical values are only indicative. The result is for a single bar. The exact value will be verified by field measurement.

How is it calculated?

  1. Enter the soil resistivity (Ω·m) (from the measurement).
  2. Enter the rod length (m) and diameter (mm).
  3. Press Calculate; the approximate grounding resistance will be displayed.

Frequently Asked Questions

How can grounding resistance be reduced?
Longer rods, multiple parallel rods (dropping to less than 1/n due to interaction), deep well electrodes, or applications that increase conductivity.
How is soil resistivity measured?
In the field, measurements are taken using the Wenner 4-probe method; the value varies depending on humidity and season.
What should the grounding resistance be in ohms?
The target varies depending on the application; generally, ≤ 2–5 Ω is targeted for many facilities, but the binding value is determined according to the relevant regulation and system type.