A cable can only be short-circuited. k²·S² ≥ I²·t It withstands (TS EN 60364-4-43); permissible opening time t_max = (k·S/I)². For example, a 25 mm² copper-XLPE (k=143) cable withstands 6 kA for 0.2 s (t_max ≈ 0.36 s).
Cable Short Circuit Withstand (I²t)
Check whether a cable can thermally withstand a potential short-circuit current and tripping time.
How is it calculated?
- Select the cable cross-section (mm²) and the k value (conductor/insulation).
- Enter the short-circuit current (kA) and tripping time (s).
- Press Calculate; the endurance and allowed time will be displayed.
Frequently Asked Questions
How to check the short-circuit withstand capability of a cable?
What is the value of k?
When is the adiabatic equation valid?