Minimum cross-section according to voltage drop criterion. A = k·ρ·L·I·cosφ / ΔU It is found using (ΔU = allowable drop, V; 3F: k=√3, 1F: k=2). For example, 400 V, 63 A, 45 m, %3 target, copper, cosφ 0.9 for ≈ 6.5 mm² → standard 10 mm².
Minimum cable cross-section from target voltage drop.
Find the minimum cable cross-section required based on the allowed voltage drop percentage. This is the inverse of the voltage drop tool.
How is it calculated?
- Select the system (1F/3F) and voltage.
- Enter the load current (A) and line length (m).
- Target %ΔU, conductor and cosφ, then press Calculate.
Frequently Asked Questions
How is cable cross-section selected based on voltage drop?
Is voltage reduction alone sufficient?
Which voltage drop limit is used?
Related tools and services
This tool and its content are for general informational purposes only; they do not constitute a binding inspection/declaration of conformity. Definitive results will be determined through on-site inspection in accordance with relevant legislation and standards. Get a quote →