The cross-section of the protective conductor (PE) is determined according to the phase cross-section: S ≤ 16 → PE = S; 16 < S ≤ 35 → PE = 16; S > 35 → PE = S/2. The main equipotential bonding conductor must be ≥ half the PE, with a minimum of 6 mm² (Cu) and an upper limit of 25 mm². For example, for a 25 mm² phase, the PE would be 16 mm² and the main busbar 10 mm².
Main Grounding / Equipotential Busbar Cross-Section
View the cross-section of the protective conductor (PE) and the main equipotential bonding conductor from the cross-section of the largest phase conductor (TS EN 60364-5-54).
How is it calculated?
- Select the largest phase conductor cross-section (mm²).
- Press Calculate; the PE and main equipotential busbar cross-sections will be displayed.
Frequently Asked Questions
What should the area of the main grounding conductor be in mm²?
What is the cross-section of a grounding conductor (electrode)?
Why is the busbar cross-section dependent on the phase cross-section?