Voltage regulation is the percentage drop in secondary voltage under load: Reg% ≈ x·(uR·cosφ + uX·sinφ). Here, uR = (Pk/S)·100, uX = √(uk²−uR²). For example, for 1000 kVA, uk = %6, Pk = 10.5 kW, full load, cosφ 0.9, uR ≈ %1.05, uX ≈ %5.91, regulation ≈ %3.52.
Transformer Voltage Regulation (%)
Calculate the secondary voltage drop (regulation) under load from the short-circuit voltage and copper loss.
How is it calculated?
- Enter the transformer power (kVA) and short-circuit voltage (uk %).
- Enter the total load copper loss (Pk) and load (%) from the label.
- Enter cosφ and secondary voltage and click Calculate.