Güç Faktörü Düzeltmesi Akımı Ne Kadar Azaltır?

At the same active power, the current is inversely proportional to the power factor: I₂/I₁ = cosφ₁/cosφ₂. Since losses are proportional to the square of the current, the loss ratio is... (cosφ₁/cosφ₂)²‘dir. Örneğin cosφ 0,75’ten 0,98’e çıkınca akım ≈ %23,5, I²R kayıpları ≈ %41,5 azalır.

Current ratio = cosφ₁/cosφ₂ · Loss ratio = (cosφ₁/cosφ₂)²
Example calculation: cosφ 0,75 → 0,98 → akım oranı 0,765; akım ≈ %23,5, I²R kayıpları ≈ %41,5 azalır. Mevcut 120 A ise yeni akım ≈ 91,8 A.

Power Factor Correction Gain (Current & Loss)

See how much the line current and I²R losses decrease when you improve the power factor (cosφ). Quantify the benefit of compensation.

Current reduction
I²R loss reduction
New trend I₂
Notes: At the same active power, I₂/I₁ = cosφ₁/cosφ₂; since line loss is proportional to the square of the current, the loss ratio is (cosφ₁/cosφ₂)². Values are calculated according to your inputs; the same level of relief is provided in cable and transformer capacity.

How is it calculated?

  1. Enter the current cosφ₁ and target cosφ₂ values.
  2. (Optional) Enter the current line current (A).
  3. Press Calculate; the current and loss reduction rates will be displayed.

Frequently Asked Questions

How much does power factor correction reduce current?
Akım oranı cosφ₁/cosφ₂ kadardır; örn. 0,75’ten 0,95’e çıkışta akım yaklaşık %21 azalır.
Why does the loss decrease more than the current?
Hat kaybı akımın karesiyle orantılıdır; akım %20 azalırsa kayıp yaklaşık %36 azalır.
What else does compensation provide?
Lower current allows for capacity relief in cables, transformers, and switchgear, resulting in reduced voltage drop and reactive power penalties.

Related tools and services

This tool and its content are for general informational purposes only; they do not constitute a binding inspection/declaration of conformity. Definitive results will be determined through on-site inspection in accordance with relevant legislation and standards. Get a quote →