What Ah capacity should a UPS battery have? (Sizing)
Required battery capacity, by dividing the energy required by the load by the battery voltage and discharge depth bulunur: Ah = (Yük × süre / verim) / (V × DoD). Örneğin 20 kW yük, 30 dk, 384 V, %80 DoD, %90 verim için ≈ 36 Ah (dizi başına) gerekir.
UPS Battery Sizing (Required Ah)
Calculate the battery capacity (Ah) required for the desired autonomy time. This is the reverse of the UPS autonomy tool: it gives the time and finds the capacity.
How is it calculated?
- Enter the load (kW) and the desired autonomy (minutes).
- Enter the battery DC voltage (V) and discharge depth (DoD %).
- Enter the inverter efficiency and click Calculate.
Frequently Asked Questions
How to size a UPS battery?
What is DoD (depth of discharge)?
Does the calculated Ah give the actual duration?