IEC 60909-0:2026 Released: What Has Changed in Short Circuit Calculations?

Short answer: The third edition of IEC 60909-0 was published in 2026 and replaced the 2016 edition. Short-circuit current is still calculated using the equivalent voltage source placed at the point of failure. The changes are mainly in the section describing how equipment is modeled: a general section for power electronic converters was added, the modeling of some wind units and some typical values changed, and most of the clause and formula numbers were changed.

Short circuit analysis is the starting point for many decisions in electrical installations, from the selection of protective devices and cable cross-section to selectivity studies and arc flash analysis. The international reference for this analysis, IEC 60909-0, is prepared by IEC Technical Committee No. 73 and reached its third edition in 2026.

Service note: AES Innovation performs short-circuit calculations and arc flash analyses with its own engineers. These studies are outside the scope of our TÜRKAK accreditation; our accreditation scope includes grounding, lightning protection, residual current protection systems, panel visual inspection and functional control, and thermography periodic checks in low-voltage installations.

What did the new edition replace?

IEC 60909-0:2026 replaced the second edition published in 2016, replacing it. The standard describes itself as a technical revision. Two main changes are listed in the preface: restructuring and completion of clauses (particularly clause 6, which describes equipment modeling) and reorganization of subscripts used in symbols.

The scope remains largely the same: low and high voltage three-phase AC systems operating at 50 Hz and 60 Hz. Systems of 550 kV and above with long transmission lines required special assessment in 2016, but are explicitly excluded from the scope in 2026. The standard also now explicitly states that it does not distinguish between grid-forming and grid-following converters (clause 1).

What remains unchanged: the essence of the method is the same.

When we read the two editions side by side, we saw that the fundamental building blocks of the calculation remained in place:

  • Equivalent voltage source method: a single voltage source of magnitude c·Un/√3 is placed at the fault point, and other voltage sources are short-circuited. The contribution of the installations modeled as current sources is added separately (clause 5.2).
  • Voltage factor c table: 1.05 (for systems with voltage tolerance ±6%) or 1.10 (±10%) for maximum current at low voltage, 0.95 or 0.90 for minimum current respectively; 1.10 and 1.00 above 1 kV (Table 1).
  • The basic formula for the grid transformer correction factor K_T (Formula 17) and the synchronous generator correction factor (now called K_SG, Formula 32).
  • The formula for the κ coefficient used for peak current is (Formula 60).
  • Basic conditions for minimum short-circuit current: correction factors are taken as 1, the contribution of the motor and wind and solar power plants is neglected, and the conductor resistance is increased according to the temperature at the end of the short circuit (clause 7.1.3).

Changes

The equipment modeling section has been rewritten.

Article 6 of the standard now addresses equipment in a more systematic order: lines and cables, transformers, reactors, capacitors, non-rotating (static) loads, grid supplies, synchronous and asynchronous machines, power electronics converters, power plant units, power plants, converter-fed motors, and finally FACTS devices and HVDC transmission systems. Shunt and series reactors and shunt and series capacitors are now described separately.

General section for power electronics converters

Fully converter solar and wind power units were also considered as current sources in the 2016 edition. However, all static converters other than those with static converter feed drives were excluded. The new edition introduces a general section for all types of power electronic converters (clause 6.10).

In summary: diode and thyristor converters generally do not require any additional input; IGBT converters, on the other hand, are typically represented by a current source provided by the manufacturer that does not exceed the device's current limit. Whether or not there is an input, and to what extent, depends on the converter's design and control.

The standard battery storage isn't explicitly mentioned. Our interpretation is this: a battery system connected via an IGBT converter could be assessed under section 6.10, while a system connected via a step-up transformer, such as a central unit, could be assessed under section 6.11.5 concerning fully-converter units. In both cases, manufacturer data is needed for the value.

Converter-fed motors

In motor drives, the determining factor is the converter on the grid side of the drive (section 6.13). Drives with grid-side diodes or thyristors generally do not contribute. Reversible drives that temporarily operate in four quadrants (e.g., rolling mill drives) are considered as asynchronous motors. The 2016 edition gave fixed values for the locked rotor current ratio and R/X for these drives; the new edition only requires the selection of a suitable ratio. Drives with IGBTs (active front-end) on the grid side are evaluated according to the rule in the converter section; a drive whose control immediately interrupts the current may not contribute at all.

Wind DFIG units and K_T

The design for dual-feed asynchronous generator (DFIG) wind units has changed. In 2016, the impedance of these units was derived from the manufacturer's peak current value; the new version uses the asynchronous generator impedance and a new correction factor (K_PD) (clause 6.11.4).

For the mains transformer, there was a second K_T formula that could be used in 2016 if the operating conditions before failure were precisely known. This alternative is not included in the new edition; only the basic formula remains.

Line data and transformer data.

The 2016 edition provided resistivity values for copper, aluminum, and aluminum alloys for overhead lines, along with a reactance formula. These are absent in the new edition; it is recommended that line and cable impedance be obtained from the manufacturer or reference sources, and that IEC TR 60909-2 be consulted for information (clause 6.2). The coefficient used to increase conductor resistance with temperature remains unchanged.

Transformer short-circuit voltage u_kr, which was defined as a percentage in 2016, is defined as a unit value (per unit) in the new edition. Those calculating manually need to correctly enter the value into the formulas.

R/X defaults for engines

To simplify the calculation, low-voltage motors, along with their connecting cables, can be represented as a single equivalent motor. The value of 5 for the ratio of the locked rotor current to the rated current has been retained. In the 2016 edition, the R/X ratio for these groups was taken as 0.42 in both the impedance calculation and the peak current coefficient. In the new edition, while the value of 0.4 is given for the equivalent group impedance, 0.42 remains only for the imaginary resistance used in the calculation of the peak current coefficient (sections 6.9.3 and 8.1).

A similar change applies to high-voltage motors and asynchronous generators. The 2016 edition provided R/X values to be used if manufacturer data was unavailable. In the new edition, if the manufacturer does not provide R/X, the machine resistance can be ignored, which, according to the standard, provides a result that is on the safe side (clause 6.9.1). The old values remain only as virtual resistance in the calculation of the peak current coefficient.

Two innovations in maximum and minimum current conditions.

The rule regarding the omission of low-contribution sources has changed direction. In 2016, fully converter-equipped power plant units could be omitted regardless of grid type if their contribution did not exceed 5% of the current calculated without these units. In the new edition, this rule covers asynchronous motors and all power plant units, but applies only to public supply systems (clause 7.1.2). The 5% threshold for omitting these sources is no longer explicitly stipulated for industrial grids.

A new note has been added to the minimum current requirements: it is stated that the arc at the fault point can significantly reduce the minimum short-circuit current, especially in systems below 1 kV and in faults at the supply inputs directly from the overhead grid (clause 7.1.3).

Numbers and symbols

Most of the item and formula numbers have changed; some numbers remain the same but indicate different content. For example, Formula 12a from 2016 is Formula 17 in the new edition, and item 6.10 (asynchronous motors) from 2016 is now the power electronics converters section in the new edition. Subscripts have also been renamed: Z_N instead of Z_Q for mains supply impedance, SG instead of G for synchronous generators, AM instead of M for asynchronous motors, and PS, PA, PD, and PC for power plant units. References to items and formulas from the old edition should be rechecked in reports and calculation notes.

Who does it affect?

  • Engineers involved in design and calculations should check which edition the calculation software is working with and which edition the report refers to. It is also beneficial to keep track of updates from the software manufacturers.
  • Battery storage and drive-intensive installations: Whether or not these converters contribute, and to what extent, depends on the device's control; the value should be obtained from the manufacturer's data.
  • Wind power plants: If the calculation is to be requested according to the new edition, the contribution of DFIG units must be re-evaluated according to the changed model.
  • Industrial networks: Since the rule allowing for the omission of small contributions up to a 5% threshold now applies only to public supply systems, it must be clearly justified which sources are being omitted from the calculation.
  • For those having arc flash analysis performed: As stated in the newly added introductory section of the standard, the short-circuit current found with IEC 60909-0 is used as input for arc current calculations, such as IEEE 1584. The new note regarding the minimum current that can be dropped by an arc should also be considered when evaluating the tripping time of the protective device.
  • Businesses with existing reports: The publication of a new edition of the standard alone does not invalidate an existing report. If the contract or specification calls for a specific edition, that should be considered; it would be reasonable to revise the calculations if batteries, inverters, or new drives have been added to the facility, or if the grid has changed.
Notes: The publication status of the European (EN) and Turkish (TS EN) equivalents of IEC 60909-0:2026 could not be verified as of the date of this writing. For the current status of the national equivalent, please refer to the TSE catalog.

Frequently Asked Questions

Has the method for calculating short circuits changed with IEC 60909-0:2026?

The core of the method remains unchanged. The equivalent voltage source method, the voltage factor c table, the basic formula for the transformer correction factor, and the formula for the peak current coefficient remain the same. The changes are mainly in the equipment modeling section: converters, wind DFIG units, motor R/X defaults, and line data.

Has my short-circuit report, prepared according to the 2016 edition, become invalid?

The publication of a new edition alone does not invalidate the report. It is necessary to consult the contract or specifications if they require a specific edition. If battery storage, inverters, or new motor drives have been added to the facility, or if the grid supply has changed, it is recommended to update the calculation.

How is the short-circuit contribution of batteries and inverters taken into account?

The standard battery storage isn't explicitly mentioned; a general rule applies to converters. IGBT converters are generally modeled as the current source in the positive component system; the upper limit of this current is taken from the manufacturer and cannot exceed the device's current limit (clause 6.10.2). Diode or thyristor converters, on the other hand, are generally not expected to contribute to the initial short-circuit current.

Why is short circuit calculation important for arc flash analysis?

In arc flash analysis, arc current and incident energy are calculated based on the short-circuit current. IEC 60909-0 provides this input; the arc current itself is found using another method such as IEEE 1584. The error in the short-circuit current is directly carried over to the arc flash result.

Sources

  • IEC 60909-0:2026, Short-circuit currents in three-phase AC systems, Part 0: Calculation of currents (3rd edition)
  • IEC 60909-0:2016, Short-circuit currents in three-phase AC systems, Part 0: Calculation of currents (2nd edition, superseded by the 2026 edition)
  • IEC TR 60909-2, Data on electrical equipment for short-circuit calculations.
  • IEEE 1584, Guidelines for Arc Flash Hazard Calculations

Relating to: Short Circuit Calculations

Relating to: Arc Flash Analysis and Labeling