Short answer: Harmonics are current and voltage components at integer multiples of the fundamental frequency of 50 Hz (150, 250, 350 Hz…); they are generated by nonlinear loads such as drives, uninterruptible power supplies (UPS) and LED drivers. THD (total harmonic distortion) is the ratio of harmonic content to the current fundamental component, while TDD (total demand distortion) is the ratio of the maximum demand current; IEEE 519 therefore specifies current limits based on TDD. For low-voltage (LV) supply voltage, EN 50160 sets an upper limit of 8% for THD; the common reference for consumer current harmonics is IEEE 519-2014.
A heated neutral wire, a circuit breaker tripping without reason, frequently replaced capacitors, or a transformer overheating at half load can all be signs of harmonics.
What are harmonics?
In the network, components whose frequency is an integer multiple of 50 Hz are called harmonics, and the number of these multiples is called the harmonic degree (h): the 3rd harmonic is 150 Hz, the 5th harmonic is 250 Hz, and the 7th harmonic is 350 Hz (TS EN 50160:2011, article 3.6; Electricity Network Regulation, article 4/1-zz).
Harmonics originate in the current. A nonlinear load draws a non-sinusoidal current under a sinusoidal voltage (IEC TR 61000-3-6:2008, clause 3.14).
Voltage distortion is a result of these currents. Harmonic currents create a voltage drop at each harmonic frequency as they pass through the transformer, cable, and network impedance (TS EN 50160:2011, clause 3.6, Note). The same load will distort the voltage much more when fed from a weak line or generator than when fed from a strong transformer. Voltage harmonics are a medium shared by everyone connected to that point; IEEE 519-2014 directs current limits to the user and voltage limits to the network operator (clauses 5.1 and 5.2).
THD and TDD: same share, different denominators
According to IEEE 519-2014, THD is the percentage ratio of the effective value of harmonic content up to the 50th order to the fundamental component; intermediate harmonics are not included (clause 3). EN 50160 calculates voltage THD up to the 40th order (EN 50160:2022+A1:2025, clause 3.3.6).
TDD divides the same share by the maximum demand current IL; IL is the average of the monthly maximum demand currents of the previous twelve months at the point of common coupling (PCC) and is the basic frequency component (IEEE 519-2014, clauses 3, 5.2 and Table 2). The Electricity Grid Regulations refer to a similar magnitude as total demand distortion (TTB) (clause 4/1-oooooo).
Since the denominator of THD-I is the current of the fundamental component, it increases as a percentage at low loads, even if the amperage of the harmonic current decreases; the grid, however, responds to amperage.
Hypothetical example: In a facility with IL = 1000 A, the fundamental component current at night is 200 A; the 5th, 7th, 11th, and 13th harmonics are 50, 30, 15, and 10 A respectively (simplified with four harmonics and instantaneous values).
- Harmonic content: √(50² + 30² + 15² + 10²) = √3725 ≈ 61 A
- THD-I = 61 / 200 ≈ 30.5%
- TDD = 61 / 1000 ≈ 6.1%
Let the daytime fundamental component be 950 A, and the harmonic content, growing at the same rate, be 75 A: THD-I = 75 / 950 ≈ 7.9%, TDD = 75 / 1000 = 7.5%. The nighttime value appears nearly four times worse, even though the harmonic current supplied to the grid is less (61 A vs. 75 A). If Isc/IL (the ratio of the maximum short-circuit current in the PCC to IL) is between 20 and 50, then in both cases the TDD remains below the 8% limit in IEEE 519-2014 Table 2; the largest component, the 5th harmonic (5% of IL at night, approximately 6.1% during the day), is also below the 7% limit. Someone looking only at THD-I might consider an unnecessary filter.
What produces harmonics?
The sources listed in IEEE 519-2014 include power electronics converters, arc furnaces, distributed generation inverters, switched-mode power supplies, and rectifiers in pulse width modulation (PWM) drives (item 1). The field equivalent is:
- Six-pulse drives, three-phase UPSs, and rectifiers predominantly produce the 5th, 7th, 11th, and 13th harmonics. In practice, the characteristic harmonics of a p-pulse rectifier are of the order pn ± 1: 5, 7, 11, 13… at six pulses, 11, 13, 23, 25… at twelve pulses; IEEE 519-2014 also states that the other orders remain significantly smaller (clause 5.5).
- LED drivers, computers, and single-phase switched-mode power supplies primarily emphasize odd multiples of 3 (3rd, 9th, 15th harmonics).
- Welding machines and arc furnaces produce interharmonics and flicker along with a constantly changing spectrum.
What do harmonics do in a facility?
In a three-phase, four-wire system, the 3rd harmonic and odd multiples of 3 are in the same phase in three phases, so they do not cancel each other out in the neutral; they add up. In single-phase offices, hospitals, and data centers with high electronic loads, the neutral current can exceed the phase current. Harmonic currents increase losses and heating in motors and transformers (IEEE 519-2014, clause 1); transformers can heat up even when loaded below their rated power. The Electrical Internal Installations Project Preparation Regulation (EİTPHY) requires that harmonic currents be considered in cable and busbar current carrying calculations (Article 10/c-1-vi).
Compensation capacitors can create resonance conditions (IEEE 519-2014, clause 1); this is often the most costly consequence in practice. The impedance of the capacitor decreases with frequency and draws harmonic current. If the compensation capacitance and the transformer and grid inductance resonate in parallel around the 5th or 7th harmonic, the impedance drawn by the harmonic current becomes very large; a small harmonic current can be converted into a large voltage distortion and overcurrent in the capacitor. The IEEE 519-2014 standard also requires calculations of total load current, resonance frequency, and reactor/capacitor ratio for harmonic loads in the compensation section of the final project (clause 10/c-4). IEEE 519-2014 also recommends that the user not add passive equipment that alters the grid impedance in a way that increases voltage distortion (clause 1.2).
In practice, these are compounded by unwanted protection tripping, inaccurate readings on measuring instruments that do not measure the true effective value (TRS), and additional heating and torque fluctuations in motors.
Relating to: Compensation Systems and Reactive Power Control
Threshold values: which criterion applies where?
The limits answer two separate questions: is the voltage you are receiving clean (EN 50160) and is your installation supplying excessive harmonic current to the grid (IEEE 519-2014; Electrical Grid Regulations for connected users)?
| Reference | Limited | Application point | Core value |
|---|---|---|---|
| EN 50160:2022+A1:2025, AG | Supply voltage | Network connection point | THD 8%, individual values are in Table 1. |
| IEEE 519-2014 Table 1, 1 kV and below | Income | Common Connection Point (PCC) | THD 8%, odd harmonics 5% |
| IEEE 519-2014 Table 2, 120 V–69 kV | User's stream | PCC | TDD 5–20%, depending on Isc/IL |
| Electricity Network Regulations, Article 13 and Annex-8, 1–34.5 kV | Current of the transmission system user | Common connection point in transmission | TDD (TTB in the Grid Regulation) 5–20%, depending on Ik/IL |
EN 50160: voltage supplied by the mains.
EN 50160 defines the expected voltage limits for the supply voltage at the grid connection point in the general network under normal operating conditions. These values are not intended to be used as electromagnetic compatibility (EMC) levels or user emission limits, and an agreement between the parties may supersede the standard (TS EN 50160:2011, clause 1.1).
In low voltage, individual harmonics are evaluated individually: under normal operating conditions, in each weekly period, 95% of the 10-minute effective values of each harmonic should not exceed the value given for that degree in Table 1. In addition, the THD, including all harmonics up to the 40th degree, should not exceed 8% (EN 50160:2022+A1:2025, clause 4.2.5). In Table 1, as a percentage of the base voltage, the 5th harmonic is 6%, the 7th harmonic 5%, the 11th harmonic 3.5%, the 13th harmonic 3%, the 3rd harmonic 5%, and the 9th harmonic 1.5%; no value is given for harmonics beyond the 25th degree. In medium voltage, the THD limit is also 8% (clause 5.2.5).
IEEE 519-2014: common port
IEEE 519 is a recommended practice; the limits are not binding in all cases (clause 1.2). The point of application is the common connection point: in the public grid, the point electrically closest to the load in question, where other loads are connected or can be connected (clause 3). In industrial installations supplied solely by a transformer, this is often the high-voltage (HV) side of the transformer; in commercial buildings supplied by a common transformer, it is the LV side (clause 1.2). The limits do not apply to a single device or panels within a facility; internal values may significantly exceed the limits recommended for the PCC (clause 5).
The evaluation is done using percentages (clause 4.4). For phase-neutral voltage harmonics, the weekly 95% short-duration (10-minute) value should be less than 1.5 times the value in Table 1, and the daily 99% very short-duration (3-second) value should be less than 1.5 times the value in Table 1 (clause 5.1). For current, the weekly 95% 10-minute value should be less than 1.5 times the value in Table 2, and the daily 99% 3-second value should be less than 2 times the value in Table 2 (clause 5.2). The current limit increases with the Isc/IL ratio (selected columns from Table 2):
| Isc/IL | TDD | 3 ≤ h < 11 (5., 7.) | 11 ≤ h < 17 (11th, 13th) |
|---|---|---|---|
| Less than 20 | 5% | 4% | 2% |
| 20–50 | 8% | 7% | 3.5% |
| 50–100 | 12% | 10% | 4.5% |
| 100–1000 | 15% | 12% | 5.5% |
| Greater than 1000 | 20% | 15% | 7% |
Values are percentages of IL; even harmonics are limited to 25% of the odd harmonic limit (Table 2 notes).
What does the legislation say in Türkiye?
The Electricity Grid Regulation is directed towards the transmission system; it covers TEİAŞ (Turkish Electricity Transmission Corporation), transmission system users, and users connected to distribution who affect transmission (Article 2). In the regulation, users are defined as production, distribution, and supply companies, as well as free consumers directly connected to the transmission system (Article 4/1-bbbb).
On the voltage side, at least 95% of the 10-minute averages of each voltage harmonic measured with a resolution of 3 seconds after event logs are extracted at common connection points in transmission must not exceed the compliance values in Annex 7 (Article 9/2). Article 9/3 sets a separate condition for total harmonic distortion: in normal operation, the THD measured when an installation or equipment is deactivated at a connection point must not exceed 3.5% at 400 kV, 5% at 154 kV, and 8% below 154 kV for a period longer than 5% of the measurement period.
On the current side, transmission system users are required to comply with the current harmonic limits in Annex 8 (Article 13/1). The TTB limits in the 1–34.5 kV column of Annex 8 are numerically the same as the TDD limits in IEEE 519-2014 Table 2; however, the values in Annex 8 are 10-minute averages and IL is the principal component of the maximum load current at the common port (Annex 8 notes).
For consumers connected to the distribution system, the distribution company may specify harmonic and power quality conditions in the connection agreement; IEEE 519 and EN 50160 are frequently used references in these conditions and project specifications. The applicable limits for a facility connected to the distribution system should be checked against the connection agreement and the current regulations of the Energy Market Regulatory Authority (EPDK).
Relating to: Reactive Energy Penalty and Compensation
IEC 61000-3-2 and IEC 61000-3-12 are product standards that limit the emissions of a single device, not the entire facility.
How is harmonic measurement performed?
IEEE 519-2014 requires that the instrument conform to IEC 61000-4-7 and IEC 61000-4-30 in comparison measurements (clause 4). The basic window is 10 periods at 50 Hz (approximately 200 ms); 15 windows of 3 seconds each, and 200 3-second values, constitute a 10-minute value (clauses 4.1–4.3). IEC 61000-4-30 defines the Class A method for contractual measurement and conformity verification; in Class A, voltage harmonics are measured to at least the 50th degree, while EN 50160 assessment requires the 40th degree (IEC 61000-4-30:2008, clauses 4.1 and 5.8.1). In the field:
- The recording takes at least a week; both standards use weekly statistics.
- Measurements are taken at the closest accessible point to the PCC (most often the LV main panel input or medium voltage measuring cell) and in large drive, UPS, and compensation panels.
- Phase voltages, phase currents, and neutral current are recorded simultaneously.
- For IL, monthly maximum demand values for the last 12 months, short-circuit current (Isc) in the PCC, transformer and compensation stage information are collected.
When are precautions necessary, and when are they not?
The decision is based on reading several checks together:
- Weekly 95% TDD and individual current harmonics at the PCC are compared to IEEE 519-2014 Table 2 or the values in your agreement using the correct Isc/IL line.
- Voltage THD and individual voltage harmonics are compared with EN 50160. If voltage distortion is high but TDD is low, the source may be the grid or neighboring facilities.
- If compensation is present, resonance is sought: capacitor without reactor, increased 5th or 7th harmonic at the tap input, heated capacitor, blown fuse.
- The neutral current is assessed by the neutral cross-section, and if heating of the transformer and cables is necessary, thermography is used.
If everything is within limits and there are no symptoms, no filter is needed; this is a valid conclusion. If there is an overshoot or resonance, the choice between reactor compensation, passive or active filtering, or source reduction is made according to the measurement data.
Relating to: Harmonic Filter Selection: Passive, Active, and Reactor-Based Solutions
Frequently Asked Questions
What should the THD level be?
For low voltage (LV), both EN 50160 and IEEE 519-2014 give an upper limit of 8%; each harmonic is also compared with its own table value. For current, there is no single correct THD-I value: IEEE 519 evaluates current using TDD, and in 120 V–69 kV systems, the limit varies between 5% and 20% depending on the Isc/IL ratio.
Is a filter necessary if the current THD is high?
No. High THD-I is often a percentage effect at low load. First, TDD, voltage distortion, and signs of resonance are evaluated in the PCC; the filter is only considered if the measurement indicates a limit overshoot or a concrete problem.
Why might the neutral current be greater than the phase current?
The third harmonic and odd multiples of 3 are in the same phase in three-phase systems; they do not cancel each other out in the neutral, but add up. Therefore, in buildings with a high single-phase electronic load, the neutral current may exceed the phase current; the neutral cross-section and the heating of the connections must be monitored.
Is there a penalty for harmonics?
The tariff texts we examined do not include a harmonic charge, which is reflected as a separate item on the bill, similar to reactive energy charges. Nevertheless, exceeding the limit is not without consequences: for transmission system users who have not installed a current harmonic measurement system, exceeding the limit is considered the case, and the relevant provisions of the Connection and System Use Agreements are applied (Electricity Network Regulation, Article 13/2). For distribution-connected facilities, the conditions in the connection agreement and the current regulations of the Energy Market Regulatory Authority (EPDK) should be consulted.
Sources
- Electricity Grid Regulations, Transmission system voltage and current harmonic limits (Articles 2, 4, 9, 13, Annex 7, Annex 8) — Official Gazette, May 28, 2014, No. 29013
- Regulation on the Preparation of Electrical Interior Installation Projects, cable calculation and compensation facility content in the final project (Article 10) — Official Gazette 3.12.2003, No. 25305
- EN 50160:2022+A1:2025, Voltage characteristics of electricity supplied by general electricity grids.
- TS EN 50160:2011, Voltage characteristics of electricity supplied by general electricity grids (Turkish version; terms and scope)
- IEEE Std 519-2014, IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power Systems
- IEC 61000-4-30:2008, Electromagnetic compatibility – Test and measurement techniques – Power quality measurement methods
- IEC TR 61000-3-6:2008, Electromagnetic compatibility – Assessment of emission limits for the connection of distorting installations to MV, HV and EHV power systems
Relating to: Power Quality Measurements
Relating to: What is Energy Analysis and How is it Performed?
Relating to: Motor Drive (VFD) Analysis
Relating to: Voltage Disturbances and Electromagnetic Compatibility (EMC)
You can contact us to schedule harmonic measurements at your facility. For a thorough assessment, we require at least one week of recordings from the main panel and large load groups, along with maximum demand information for the past 12 months and transformer data.