Number of down conductors, by dividing the building perimeter into typical intermediate distances It is present and is at least 2. Typical spacing according to TS EN 62305-3: LPL I–II 10 m, LPL III 15 m, LPL IV 20 m. For example, a 40×20 m structure (perimeter 120 m) requires approximately 8 down conductors for LPL III.
Number of Downstream (Downstream) Conductors
See the approximate number of down conductors required according to the building environment and protection level (LPL) (TS EN 62305-3).
How is it calculated?
- Enter the length and width (m) of the structure.
- Select the Level of Protection (LPL).
- Press Calculate; the perimeter, spacing, and number of down conductors will be displayed.