Düşey çubuk elektrotun topraklama direnci R = ρ/(2πL)·(ln(8L/d)−1) ile bulunur: toprak özdirenci (ρ), çubuk boyu (L) ve çapı (d) kullanılır. Örneğin ρ=100 Ω·m, 3 m boy, 16 mm çap için R ≈ 33,5 Ω. Toprak özdirenci ölçümle (Wenner) belirlenir.

R = ρ/(2πL)·(ln(8L/d) − 1) [Ω]
Example calculation: ρ=100 Ω·m, 3 m boy, 16 mm çap çubuk → R = 100/(2π×3)·(ln(8×3/0,016)−1) ≈ 33,5 Ω. Daha düşük direnç için daha uzun/çok çubuk gerekir.

Grounding Resistance (Rod Electrode)

Calculate the approximate grounding resistance of a single-rod electrode from the soil resistivity and rod dimensions.

Grounding resistance
The ρ used
Notes: R = ρ/(2πL)·(ln(8L/d)−1) (BS 7430 / IEEE 142 — vertical bar). Soil resistivity ρ is determined by measurement (Wenner 4-prong method). And it varies depending on the season/humidity; typical values are only indicative. The result is for a single bar. The exact value will be verified by field measurement.

How is it calculated?

  1. Toprak özdirencini (Ω·m) girin (ölçümden).
  2. Çubuk boyunu (m) ve çapını (mm) girin.
  3. Hesapla’ya basın; yaklaşık topraklama direnci görüntülenir.

Frequently Asked Questions

Topraklama direnci nasıl düşürülür?
Daha uzun çubuk, birden fazla paralel çubuk (karşılıklı etkileşim nedeniyle 1/n’den az düşer), derin kuyu elektrotu veya iletkenliği artıran uygulamalarla.
Toprak özdirenci nasıl ölçülür?
Sahada Wenner 4-uçlu yöntemiyle ölçülür; değer nem ve mevsime göre değişir.
Topraklama direnci kaç ohm olmalı?
Hedef uygulamaya göre değişir; birçok tesis için genel olarak ≤ 2–5 Ω hedeflenir, ancak bağlayıcı değer ilgili yönetmelik ve sistem türüne göre belirlenir.

Related tools and services

This tool and its content are for general informational purposes only; they do not constitute a binding inspection/declaration of conformity. Definitive results will be determined through on-site inspection in accordance with relevant legislation and standards. Get a quote →