Trafo Yüklenme Oranı Nasıl Hesaplanır?

Transformer loading, It is the ratio of the apparent power drawn (S_load = P/cosφ) to the rated power.: %yüklenme = S_yük / S_anma × 100. Örneğin 1000 kVA trafodan 620 kW (cosφ 0,9) çekiliyorsa görünür yük ≈ 689 kVA, yani ≈ %69 yüklenme. Sürekli çalışmada tipik uygun aralık %40–80’dir.

%Yurning = (P/cosφ) / S_rated × 100 · I = S_load/(√3·U)
Example calculation: 1000 kVA trafo, 620 kW yük, cosφ 0,9 → görünür yük 620/0,9 ≈ 689 kVA → yüklenme ≈ %69 (uygun aralık); sekonder akım ≈ 994 A.

Transformer Load Ratio (%)

Calculate the transformer's percentage load and secondary current based on its rated power; identify over/under loads.

Load rate
Apparent load S
Secondary current
Notes: Yüklenme = (P/cosφ) / S_anma · Sekonder akım = S_yük/(√3·U). Uygun süreklilik aralığı tipik %40–80'dir (verim ve yedek marj açısından); >%100 aşırı yüklenmedir. Kesin değerlendirme yük profili ve ortam sıcaklığına göre yapılır.

How is it calculated?

  1. Enter the transformer power (kVA) and secondary voltage.
  2. Enter the active power drawn (kW) and cosφ.
  3. Press Calculate; the load %, apparent load, and secondary current will be displayed.

Frequently Asked Questions

What percentage load should the transformer be subjected to?
Sürekli çalışmada tipik olarak %40–80 aralığı verim ve yedek marj açısından uygundur; %100 üzeri aşırı yüklenmedir.
What happens if the transformer is overloaded?
Winding temperature and aging increase, lifespan shortens, and protection may trip. Load reduction or capacity increase is required.
Why is low load inefficient?
At very low loads, iron (no-load) loss becomes dominant and efficiency decreases; the transformer operates below its optimum point.

Related tools and services