Approximate short-circuit current in the transformer secondary. I_k ≈ I_n × 100 / uk It is found with; the full load current is I_n = S / (√3·U). For example, in a 1000 kVA, 400 V, UK %6 transformer, I_n ≈ 1443 A and I_k ≈ 24 kA (assuming infinite busbar, upper limit).
Transformer Full Load & Short Circuit Current
Calculate the full-load current and approximate short-circuit current in the transformer secondary (preliminary information for panel/breaker selection).
How is it calculated?
- Enter the transformer power (kVA) and secondary voltage (V).
- Enter the short-circuit voltage (UK %) from the label.
- Press Calculate; the full load and short-circuit current will be displayed.
Frequently Asked Questions
How to find the transformer short-circuit current?
What is short circuit voltage (UK)?
Is this value the actual fault current?
Related tools and services
This tool and its content are for general informational purposes only; they do not constitute a binding inspection/declaration of conformity. Definitive results will be determined through on-site inspection in accordance with relevant legislation and standards. Get a quote →